Calculateur Watts en Ampères

Instantly convert Watts (W) or Kilowatts (kW) to Amps (A) for DC, single-phase AC, and three-phase AC electrical circuits with step-by-step formulas and breaker sizing.

Select Current Type (DC / Single-Phase AC / Three-Phase AC)

Residential & commercial outlets, appliances, and lighting (120V / 230V / 240V).

Real electrical power (P)
Quick Watts:
Electromotive potential (V)
V
Standard 1-Phase AC Voltages:
Range: 0.01 to 1.00
cos(φ)
Electrical Current Result (Single-Phase AC)
12.5 A(12,500 mA)
Real Power
1,500 W (1.5 kW)
Apparent Power
1,500 VA
Equivalent Load R
9.6 Ω
Single-Phase AC Current Formula
Amps (A) = Watts (W) ÷ (Volts (V) × Power Factor)
Step 1: Multiply Voltage by Power Factor (PF)
V × PF = 120 V × 1 = 120 V_eff
Step 2: Divide Real Power (W) by Effective Voltage
I = 1,500 W ÷ 120 = 12.5 A
125% Continuous Load Safety Margin: 15.63 A

For continuous loads running 3 hours or more (NEC 210.20), circuits are sized at 125% of operating current. Minimum standard breaker rating: 20 A.

Quick Watts to Amps Reference Chart (12V DC, 120V AC & 240V AC)

Instant reference comparing electrical current draw (in Amps) across common wattage ratings for 12V DC battery systems and 120V / 240V single-phase AC household circuits (at PF = 1.0 and PF = 0.85).

Power (Watts)12V DC (Amps)120V AC (PF 1.0)120V AC (PF 0.85)240V AC (PF 1.0)
100 W8.33 A0.83 A0.98 A0.42 A
300 W25 A2.5 A2.94 A1.25 A
600 W50 A5 A5.88 A2.5 A
1,000 W83.33 A8.33 A9.8 A4.17 A
1,500 W125 A12.5 A14.71 A6.25 A
2,000 W166.67 A16.67 A19.61 A8.33 A
2,400 W200 A20 A23.53 A10 A
3,000 W250 A25 A29.41 A12.5 A
5,000 W416.67 A41.67 A49.02 A20.83 A

About the Calculateur Watts en Ampères

The **Watts to Amps Calculator** is a precision electrical conversion tool that converts real electrical power in **Watts (W)** or **Kilowatts (kW)** into electric current in **Amperes (Amps, A)**. Whether you are sizing wires and fuses for a 12V/24V/48V DC solar battery bank, checking how many amps a 1,500W space heater draws on a 120V household outlet, or calculating line current for a 480V three-phase industrial motor, this **Watts to Amps Conversion Calculator** delivers instant, accurate results. Because electrical current depends on both system voltage and whether the supply is Direct Current (DC) or Alternating Current (AC), a reliable **Watt to Amp Calculator** must account for circuit phase configuration and **Power Factor (PF)**. Use the mode selector above to switch seamlessly between DC, Single-Phase AC, and Three-Phase AC calculations.

How to Use This Calculator

  1. 1Select your electrical system mode at the top of the **Watts to Amps (A) Calculator**: **Direct Current (DC)**, **Single-Phase AC**, or **Three-Phase AC**.
  2. 2Enter the electrical power consumption in **Watts (W)** or switch the unit toggle to **Kilowatts (kW)**.
  3. 3Enter the supply **Voltage (Volts)** or click one of the standard voltage presets (such as 12V, 24V, 120V, 208V, 230V, 240V, or 480V).
  4. 4For Single-Phase AC and Three-Phase AC modes, enter the **Power Factor (PF)** between 0.01 and 1.00 (use 1.00 for purely resistive appliances or 0.80–0.85 for inductive motor loads).
  5. 5Review the instant current output in **Amps (A)** and **Milliamps (mA)**, the active formula, step-by-step calculation breakdown, and the 125% continuous-load breaker recommendation.

Formula & Calculation Methodology

To **convert Watts to Amps**, the governing formula depends on whether the circuit operates on Direct Current (DC), Single-Phase Alternating Current (AC), or Three-Phase Alternating Current (AC): ### 1. DC Watts to Amps Formula In a direct current circuit, voltage and current are constant and in phase, so the relationship follows Watt's Law directly: $$\text{Amps (A)} = \frac{\text{Watts (W)}}{\text{Volts (V)}}$$ ### 2. Single-Phase AC Watts to Amps Formula In a single-phase AC circuit, inductive or capacitive loads cause a phase difference between voltage and current, represented by the **Power Factor ($\text{PF}$)** ($0 < \text{PF} \le 1.0$): $$\text{Amps (A)} = \frac{\text{Watts (W)}}{\text{Volts (V)} \times \text{Power Factor (PF)}}$$ ### 3. Three-Phase AC Watts to Amps Formula (Line-to-Line Voltage) In a balanced three-phase AC system where voltage is measured line-to-line ($V_{LL}$), power is distributed across three phases offset by $120^\circ$, introducing a factor of $\sqrt{3} \approx 1.73205$: $$\text{Amps (A)} = \frac{\text{Watts (W)}}{\sqrt{3} \times \text{Volts (V)} \times \text{Power Factor (PF)}}$$

Worked Example: Converting Watts to Amps Across DC, Single-Phase AC, and Three-Phase AC

Scenario: Let us calculate the electrical current in Amps (A) for three common real-world scenarios: a 1,500W household space heater at 120V AC (PF = 1.0), a 600W DC load on a 12V battery bank, and a 10,000W three-phase industrial compressor at 480V AC (PF = 0.85).

Example 1: Single-Phase AC Appliance (1,500W at 120V, PF = 1.0): Amps = 1,500 W / (120 V × 1.0)
12.50 A (15.63 A at 125% continuous load)
Example 2: 12V DC Battery / Solar Load (600W at 12V DC): Amps = 600 W / 12 V
50.00 A
Example 3: Three-Phase AC Industrial Motor (10,000W at 480V, PF = 0.85): Amps = 10,000 W / (1.73205 × 480 V × 0.85) = 10,000 / 706.6767
14.15 A per phase
Conclusion: Higher system voltages dramatically reduce the current in Amps required to deliver the same wattage, while AC inductive loads with a Power Factor below 1.0 draw proportionally more current than resistive loads.

Assumptions & Practical Limitations

  • Calculations represent steady-state RMS electrical current from real power (Watts) and nominal supply voltage.
  • Electric motors, air conditioners, and compressors draw transient inrush (locked-rotor) startup current that can be 3 to 7 times higher than steady running amps.
  • DC-to-AC power inverters typically operate at 85%–95% efficiency; divide AC output wattage by inverter efficiency before calculating DC battery current.
  • Per National Electrical Code (NEC 210.20), continuous loads operating for 3 hours or more require conductors and overcurrent protection sized at 125% of continuous current.

Frequently Asked Questions

At 120 volts AC with a unity power factor (PF = 1.0, typical for space heaters, hair dryers, and toasters), 1,500 watts equals 12.5 amps (1500 W ÷ 120 V = 12.5 A). If the load has a power factor of 0.85, it draws 14.71 amps.